HDGC3985 Battery Activation 380V Battery String


General information
 
Battery Charge Discharge Tester is mainly used for the charge test of battery of the backup power supply in the telecommunications, mobile, substation, railway transportation and pertrochemical industry power DC industries. It can proceed the discharge and charge for the batteries to extend the lift-time .
 
Features
 
● PTC ceramic resistor is used to avoid red heat for a safer discharge process.
● PC software can record and analyze the total voltage, discharge current, each cell voltage and other data, and generate the data reports accordingly, to visually show the battery group performance curve, graph, report, etc for printing and checking.
● The USB interface of the tester can store the data of the discharge process into the USB flash drive, which is imported into PC. The PC data management software can analyze the battery discharge process and generate corresponding data reports, further facilitating the data transfer and storage.
● Intelligent SCM ARM control, 7-inch 1024*600 HD LCD display, capacitive touch control operation, built-in Chinese-English switch menu, and simple and clear menu operation.
● Automatic stop protection function, over-temperature protection, over-voltage protection, over-current protection, reverse wiring protection, alarm prompt on screen upon any alarm stop, and automatic switch-off of the air circuit breaker.
● It can set charge/discharge stop condition including low cell battery voltage.
● The conditions of charge/discharge termination can be set, including cell low voltage, group low/high voltage, small charge current, charge/discharge time, and charge/discharge capacity. When any of the conditions are met, the tester will automatically stop testing with buzzer prompt and automatically record the reason for stop at the same time.
● Online compensated charging/discharging can be carried out, and the discharge test can be carried out on the online working battery through an externally connected current clamp sensor, which greatly facilitates the testing work. This feature is especially suitable for applications where there is only a single set of backup batteries.
● It can perform on-line compensated charge/discharge, it can carry on discharge test for on-line working storage battery by connection external current clamp sensor,which is convenient for measurement job. The function is suitable for only single set of backup battery .
● RS485 remote control charge , discharge and activation functions .
● It has the functions of charge, discharge and activation in multi-machine  parallel mode by only operating in the display screen of the parallel instrument with parameters as the master. The instrument with parameters as the slave can automatically follow the master’s instructions to distribute power evenly, and start or stop operation.

Technical Specifications

Suitable Battery DC 380V Battery Pack
Model No. HDGC3985 HDGC3985
Discharge Voltage Range DC 300V-460V DC 300V-460V
Discharge Current Range 0-50A 0-50A
Charge Voltage Range DC 300V-450V DC 300V-450V
Charge Current Range 0-10A 0-20A
Working mode Standalone mode, parallel master mode, parallel slave mode, and remote controlled mode
Protection performance  Over-voltage protection, under-voltage stop, over-current protection, reverse wiring protection, 65℃ over-temperature protection, – LCD prompt and buzzer alarm
Cell voltage collection (optional) Multi-band RF wireless module for communication distance within 100m, compatible with 2V/4V/6V/12V cell voltage monitoring, 1-25 groups of RF wireless monitoring modules for monitoring up to 300 batteries, and single wireless monitoring module for monitoring 12 cells
Control precision Discharge current≤±1%; group voltage≤±0.1%; cell voltage≤±0.1%
PC communication RS485 interface, USB interface
Work Environment
Heat radiation Forced air cooling
Temperature Working rage: -5-50℃  Storage temperature: -40-70℃
Humidity Relative humidity 0-90% (40±2℃)
Elevation Rated elevation of 4,000m
Noise ﹤75dB
Working Power Supply
Voltage Power supply: single-phase AC220V (-20%-+30%), frequency: 45-65Hz; charging power supply: refer to nameplate parameters or case label
Electric strength test Input-shell: 2200Vdc 1min
Input-output: 2200Vdc 1min
Output-shell: 700Vdc 1min
Safety Compliance with EN610950